The list below is now frozen for installation.
| COUNT | CABLE TYPE | FROM | TO | LENGTH | CONN | DESCRIPTION | RATINGS | NOTE |
|---|---|---|---|---|---|---|---|---|
| 1. CABLES FROM MTA EXPERIMENTAL HALL TO LINAC GALLERY VIA BERM TROUGH (along west wall across center) | ||||||||
| 8 | Belden 9332 | Linac LK8-6 | MTA ExpHall east | 360 | 9-pair multiconductor cable absorber diagnostics |
PLTC/ITC/CMG | 1, 2 | |
| 4 | Optical fiber | Linac LK8-6 | MTA ExpHall east | 360 | 50/125u breakout cable L-Com FOB500B2-M absorber diagnostics |
OFNP | 1, 2 | |
| 4 | 1/2 inch heliax | Linac LK8-6 | MTA ExpHall center | 360 | N | rf diagnostics | CATVR | |
| 4 | 1/2 inch heliax | Linac RF7 | MTA ExpHall center | 410 | N | rf diagnostics | CATVR | |
| 16 | 1/4 inch heliax | Linac LK8-6 | MTA ExpHall center | 360 | N | rf diagnostics | CATVR | |
| 4 | 1/4 inch heliax | Linac RF7 | MTA ExpHall center | 410 | N | rf diagnostics | CATVR | |
| 12 | RG 58/U green | Linac LK8-6 | MTA ExpHall center | 360 | BNC | rf diagnostics | fire rated | |
| 12 | RG 58/U red | Linac LK8-6 | MTA ExpHall center | 360 | SHV | high voltage for rf diagnostics | fire rated | |
| 2 | Okonite 261-10-2208 | Linac LK8-6 | MTA ExpHall | 360 | 8 twisted pair, shielded | ITC/PLTC Class I-Division 2 |
1 | |
| 2. CABLES FROM MTA EXPERIMENTAL HALL (southeast corner) TO REFRIGERATION ROOM (northwest corner and north wall) | ||||||||
| 4 | 1/2 inch heliax | RefRm rack through 12 |
MTA ExpHall center through 12 |
150 | N | rf diagnostics | CATVR | |
| 8 | 1/4 inch heliax | RefRm rack through 12 |
MTA ExpHall center through 12 |
150 | N | rf diagnostics | CATVR | |
| 8 | RG 58/U green | RefRm rack through 6 |
MTA ExpHall center through 6 |
150 | BNC | rf diagnostics | fire rated | |
| 8 | RG 58/U red | RefRm rack through 7 |
MTA ExpHall center through 7 |
150 | SHV | high voltage for rf diagnostics | fire rated | |
| 1 | Optical fiber | RefRm rack through 7 |
MTA ExpHall center through 7 |
150 | ST | 62.5/125u breakout cable GPIB link |
OFNP | 1 |
| 6 | RG 59/U | RefRm rack through 7 |
MTA ExpHall through 7 |
150 | BNC | Belden 1506A, video | plenum, NFPA262 | 3 |
| 2 | Belden 9332 | RefRm rack through 7 |
MTA ExpHall east through 7 |
9-pair multiconductor cable absorber diagnostics |
PLTC/ITC/CMG | 1, 2 | ||
| 2 | Okonite 261-10-2208 | RefRm southeast through 7 |
MTA ExpHall through 7 |
180 | radiation interlocks 8 pair, shielded |
ITC/PLTC Class I-Division 2 |
1 | |
| 8 | Okonite 284-20-1401 | RefRm near Neslab through 6 |
MTA ExpHall center through 6 |
150 | thermocouple wire single twisted pair |
ITC/PLTC Class I-Division 2 |
1 | |
| 4 | 500 MCM Cable | RefRm near Neslab through 5 |
MTA ExpHall center to magnet through 5 |
160 | braided Cu cable for solenoid power | |||
| 8 | Okonite 264-10-3301 | RefRm near Neslab through 6 |
MTA ExpHall through 6 |
150 | 1 twisted pair, shielded | ITC/PLTC Class I-Division 2 |
1 | |
| 3. CABLES FROM REFRIG. ROOM THROUGH THE MTA EXP. HALL (along south and west walls) AND BERM TROUGH, TO 805MHZ STATION | ||||||||
| 1 | Optical fiber | Linac LK8-6 through ExpHall 7 |
MTA RefRm through 7 |
525 | ST | 62.5/125 breakout cable GPIB link |
OFNP | 1 |
| 4 | RG 59/U | Linac LK8-6 through ExpHall 7 |
MTA RefRm through 7 |
525 | BNC | Belden 1506A, video | plenum, NFPA262 | 3 |
| 4. CABLES FROM MTA EXPERIMENTAL HALL TO LINAC GALLERY LOWER LEVEL VIA BERM TROUGH | ||||||||
| 7 | RG 58/U green | Rad Safety MUX Box | MTA ExpHall, ? | 300 | Radiation safety cables to Linac lower level near blue stairs | 4 | ||
| 5. CABLES WITHIN MTA EXPERIMENTAL HALL | ||||||||
| 4 | 500 MCM Cable | MTA ExpHall southwest corner |
MTA ExpHall center to magnet |
? | braided Cu cable for solenoid power | 5 | ||
| Yagmur Torun | March 30, 2005 |